Condition Input each package

Condition Input: Premium

1. Total losses value Min 300 W to Max 35000 W

2. Tank height Min 600 mm to Max 1500 mm. And ratio of tank height to average (inner and outer ) of number of stands in Axial multiply stand dimension in axial are Min 2.1 to Max 3.5.

3. Dissipation area/Total losses Min 23.5 Sq.cm/W to Max 41 Sq.cm/W

4. Ratio of coil thickness (conductor only) / coil thickness(including layer insulation but not including inner ducts) Min 0.6 to Max 0.95

5. Number of inner ducts Min 0 to Max 6

6. Inner duct thickness Min 2 mm to Max 6 mm

7. Max outer coil thickness 65 mm and Max inner coil thickness 40 mm ( DIA_OUT-DIA_IN)/2

8. Percentage of Winding AC Losses/Transformer rating , Min 0.52% to Max 1.8 %

9. Percentage of Total losses / Transformer rating, Min 0.7% To 2 %

10. Ratio of Actual heat dissipation area / Initial heat dissipation area, Min 0.75 To Max 1.4

11. Ratio of Inner AC winding losses/Outer AC winding losses, Min 0.5 To Max 1.2

Remark Condition Input A2 Total losses < 140,000 w and others as appropriate for the design


Condition Input: Professional Plus ,Professional, Basic plus

1. Total losses value Min 300 W to Max 20000 W

2. Tank height Min 600 mm to Max 1500 mm. And ratio of tank height to average (inner and outer ) of number of stands in Axial multiply stand dimension in axial are Min 2.1 to Max 3.5.

3. Dissipation area/Total losses Min 23.5 Sq.cm/W to Max 41 Sq.cm/W

4. Ratio of coil thickness (conductor only) / coil thickness(including layer insulation but not including inner ducts) Min 0.6 to Max 0.95

5. Number of inner ducts Min 0 to Max 6

6. Inner duct thickness Min 2 mm to Max 6 mm

7. Max outer coil thickness 65 mm and Max inner coil thickness 40 mm ( DIA_OUT-DIA_IN)/2

8. Percentage of Winding AC Losses/Transformer rating , Min 0.52% to Max 1.8 %

9. Percentage of Total losses / Transformer rating, Min 0.7% To 2 %

10. Ratio of Actual heat dissipation area / Initial heat dissipation area, Min 0.75 To Max 1.4

11. Ratio of Inner AC winding losses/Outer AC winding losses, Min 0.5 To Max 1.2


Condition Input: Basic

1. Total losses value Min 300 W to Max 5000 W

2. Tank height Min 600 mm to Max 1500 mm. And ratio of tank height to average (inner and outer ) of number of stands in Axial multiply stand dimension in axial are Min 2.1 to Max 3.5.

3. Dissipation area/Total losses Min 23.5 Sq.cm/W to Max 41 Sq.cm/W

4. Ratio of coil thickness (conductor only) / coil thickness(including layer insulation but not including inner ducts) Min 0.6 to Max 0.95

5. Number of inner ducts Min 0 to Max 6

6. Inner duct thickness Min 2 mm to Max 6 mm

7. Max outer coil thickness 65 mm and Max inner coil thickness 40 mm ( DIA_OUT-DIA_IN)/2

8. Percentage of Winding AC Losses/Transformer rating , Min 0.52% to Max 1.8 %

9. Percentage of Total losses / Transformer rating, Min 0.7% To 2 %

10. Ratio of Actual heat dissipation area / Initial heat dissipation area, Min 0.75 To Max 1.4

11. Ratio of Inner AC winding losses/Outer AC winding losses, Min 0.5 To Max 1.2